Heat transfer condensation tests for three widely used refrigerants (R-22, R-134a, R-407C) condensing inside a smooth tube are reported. The experimental runs to measure the heat transfer coefficients are carried out at an average saturation temperature of 40°C, at mass velocities ranging from 100 to 750 kg/(m2 s), over the entire vapour quality range. For R-134a condensation tests at 30, 50, and 60°C saturation temperature are also presented. In the case of R-407C, in-line concentration measurements are carried out by means of a gas chromatograph

Comparison of condensation heat transfer of three widely used refrigerants (R-22, R-134a, R-407C)

ROSSETTO, LUISA;CENSI, GIUSEPPE;DEL COL, DAVIDE;DORETTI, LUCA;LONGO, GIOVANNI ANTONIO;ZILIO, CLAUDIO
2000

Abstract

Heat transfer condensation tests for three widely used refrigerants (R-22, R-134a, R-407C) condensing inside a smooth tube are reported. The experimental runs to measure the heat transfer coefficients are carried out at an average saturation temperature of 40°C, at mass velocities ranging from 100 to 750 kg/(m2 s), over the entire vapour quality range. For R-134a condensation tests at 30, 50, and 60°C saturation temperature are also presented. In the case of R-407C, in-line concentration measurements are carried out by means of a gas chromatograph
2000
Atti del 18° Congresso Nazionale di Trasmissione del Calore
File in questo prodotto:
Non ci sono file associati a questo prodotto.
Pubblicazioni consigliate

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11577/2429810
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus ND
  • ???jsp.display-item.citation.isi??? ND
social impact