In order to achieve the reduction of voltage distortion in ac power supplies (ACPSs), this paper describes an implementation of synchronous-frame control for selected frequencies in the output voltage. The regulation of the fundamental output voltage, as well as that of some low-order harmonics, is achieved using a synchronous-frame controller for each selected frequency in addition to a conventional control. The conventional part conserves good dynamic performance under load changes, while rotating-frame controllers allow a slow, but very precise compensation of the residual errors within the assumption that the harmonics produced by distorting load are slowly varying. Moreover, motivated by a fixed-point implementation, a set of refinements and modifications of the original scheme is proposed, allowing a reduction of signal processing requirements and a new control algorithm structure less sensitive to quantization and rounding errors. This solution is particularly effective for high-power fully digitally controlled ACPSs, where the voltage loop bandwidth is usually not large enough to provide regulation at harmonic frequencies. The proposed control scheme has been implemented using a fixed-point single-chip digital signal processor (ADMC401 by Analog Devices). Experimental results on a 3-kVA three-phase converter prototype show the effectiveness of the proposed approach.

Synchronous frame harmonic control for high-performance AC power Supplies

MATTAVELLI, PAOLO
2001

Abstract

In order to achieve the reduction of voltage distortion in ac power supplies (ACPSs), this paper describes an implementation of synchronous-frame control for selected frequencies in the output voltage. The regulation of the fundamental output voltage, as well as that of some low-order harmonics, is achieved using a synchronous-frame controller for each selected frequency in addition to a conventional control. The conventional part conserves good dynamic performance under load changes, while rotating-frame controllers allow a slow, but very precise compensation of the residual errors within the assumption that the harmonics produced by distorting load are slowly varying. Moreover, motivated by a fixed-point implementation, a set of refinements and modifications of the original scheme is proposed, allowing a reduction of signal processing requirements and a new control algorithm structure less sensitive to quantization and rounding errors. This solution is particularly effective for high-power fully digitally controlled ACPSs, where the voltage loop bandwidth is usually not large enough to provide regulation at harmonic frequencies. The proposed control scheme has been implemented using a fixed-point single-chip digital signal processor (ADMC401 by Analog Devices). Experimental results on a 3-kVA three-phase converter prototype show the effectiveness of the proposed approach.
2001
File in questo prodotto:
Non ci sono file associati a questo prodotto.
Pubblicazioni consigliate

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11577/1480218
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 237
  • ???jsp.display-item.citation.isi??? 185
  • OpenAlex 259
social impact