This paper presents the heat transfer coefficients and the pressure drop measured during HFO1234yf condensation inside a brazed plate heat exchanger: the effects of saturation temperature, refrigerant mass flux and vapour superheating are investigated. The heat transfer coefficients show weak sensitivity to saturation temperature and great sensitivity to refrigerant mass flux. At low refrigerant mass flux (< 20 kg/m2s) the heat transfer coefficients are not dependent on mass flux and condensation is controlled by gravity. For higher refrigerant mass flux (> 20 kg/m2s) the heat transfer coefficients depend on mass flux and forced convection ondensation occurs. The condensation heat transfer coefficients of super-heated vapour are from 8 to 11% higher than those of saturated vapour. The frictional pressure drop shows a linear dependence on the kinetic energy per unit volume of the refrigerant flow and therefore a quadratic dependence on the refrigerant mass flux. HFO1234yf exhibits heat transfer coefficients lower (10-12%) and frictional pressure drop lower (10-20%) than those of HFC134a under the same operating conditions.

HFO1234yf Condensation Inside a Brazed Plate Heat Exchanger

LONGO, GIOVANNI ANTONIO;ZILIO, CLAUDIO
2012

Abstract

This paper presents the heat transfer coefficients and the pressure drop measured during HFO1234yf condensation inside a brazed plate heat exchanger: the effects of saturation temperature, refrigerant mass flux and vapour superheating are investigated. The heat transfer coefficients show weak sensitivity to saturation temperature and great sensitivity to refrigerant mass flux. At low refrigerant mass flux (< 20 kg/m2s) the heat transfer coefficients are not dependent on mass flux and condensation is controlled by gravity. For higher refrigerant mass flux (> 20 kg/m2s) the heat transfer coefficients depend on mass flux and forced convection ondensation occurs. The condensation heat transfer coefficients of super-heated vapour are from 8 to 11% higher than those of saturated vapour. The frictional pressure drop shows a linear dependence on the kinetic energy per unit volume of the refrigerant flow and therefore a quadratic dependence on the refrigerant mass flux. HFO1234yf exhibits heat transfer coefficients lower (10-12%) and frictional pressure drop lower (10-20%) than those of HFC134a under the same operating conditions.
2012
International Refrigeration and Air Conditioning Conference at Purdue
File in questo prodotto:
Non ci sono file associati a questo prodotto.
Pubblicazioni consigliate

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11577/2532336
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus ND
  • ???jsp.display-item.citation.isi??? ND
  • OpenAlex ND
social impact