In this paper the optimal energy efficiency and high pressure problem in single stage transcritical carbon dioxide vapour compression units is addressed. A real-time model-based optimisation algorithm for the optimal (or quasi-optimal, close to the optimal) pressure determination is developed as a more efficient and robust solution than literature approximated ones. The problem is solved by a model estimating the system performance and by measuring its boundary conditions. The model is obtained by an on-line artificial neural network identification technique and the optimisation problem is worked out by a particle swarm technique. The proposed algorithm is dynamically tested by simulation, considering the performance of a supply water temperature controlled carbon dioxide heat pump. It appears to successfully approximate the optimal cycle discharge pressure showing an average daily pressure deviation of 0.9 × 105Pa over a two years simulation period, corresponding to 1.1% increase in the cumulated energy consumption, compared to the optimal pressure solution. © 2012 Elsevier Ltd and IIR. All rights reserved.

A real-time algorithm for the determination of \R744\ systems optimal high pressure

CECCHINATO, LUCA;CORRADI, MARCO;MINETTO, SILVIA;RAMPAZZO, MIRCO
2012

Abstract

In this paper the optimal energy efficiency and high pressure problem in single stage transcritical carbon dioxide vapour compression units is addressed. A real-time model-based optimisation algorithm for the optimal (or quasi-optimal, close to the optimal) pressure determination is developed as a more efficient and robust solution than literature approximated ones. The problem is solved by a model estimating the system performance and by measuring its boundary conditions. The model is obtained by an on-line artificial neural network identification technique and the optimisation problem is worked out by a particle swarm technique. The proposed algorithm is dynamically tested by simulation, considering the performance of a supply water temperature controlled carbon dioxide heat pump. It appears to successfully approximate the optimal cycle discharge pressure showing an average daily pressure deviation of 0.9 × 105Pa over a two years simulation period, corresponding to 1.1% increase in the cumulated energy consumption, compared to the optimal pressure solution. © 2012 Elsevier Ltd and IIR. All rights reserved.
File in questo prodotto:
Non ci sono file associati a questo prodotto.
Pubblicazioni consigliate

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11577/2759284
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 49
  • ???jsp.display-item.citation.isi??? 47
  • OpenAlex ND
social impact