This paper presents the local heat transfer coefficients of R290 (propane) and R1270 (propylene) boiling inside a Brazed Plate Heat Exchanger (BPHE). A new test section was designed for measuring the local heat transfer coefficient in refrigerant two-phase heat transfer in a BPHE. The test section includes two thick AISI316L stainless steel corrugated plates instrumented with 36 T-type thermocouples for measuring the local plate surface temperature, the local heat flux and the local heat transfer coefficient in 9 positions along the refrigerant channel. The experimental tests were carried out at a boiling temperature of 10 °C, in the refrigerant mass flux range 5 − 17.5 kg m−2 s−1 with an inlet vapour quality ranging from 0.24 to 0.37 and an outlet vapour quality around 1.00. The global uncertainty of the local heat transfer coefficient measurement is within ±12.7%, and ±15.6%, for R290, and R1270, respectively. Nucleate boiling seems to be the governing heat transfer regime both in R290 and R1270 tests. Consolidated correlations for nucleate boiling inside BPHE show a fair agreement with all the experimental data. R290 and R1270 exhibit boiling heat transfer performance between those of R404A and those of R410A.

Hydrocarbon refrigerants boiling local heat transfer coefficients inside a Brazed Plate Heat Exchanger (BPHE)

Longo G. A.;Mancin S.;Righetti G.;Zilio C.
2023

Abstract

This paper presents the local heat transfer coefficients of R290 (propane) and R1270 (propylene) boiling inside a Brazed Plate Heat Exchanger (BPHE). A new test section was designed for measuring the local heat transfer coefficient in refrigerant two-phase heat transfer in a BPHE. The test section includes two thick AISI316L stainless steel corrugated plates instrumented with 36 T-type thermocouples for measuring the local plate surface temperature, the local heat flux and the local heat transfer coefficient in 9 positions along the refrigerant channel. The experimental tests were carried out at a boiling temperature of 10 °C, in the refrigerant mass flux range 5 − 17.5 kg m−2 s−1 with an inlet vapour quality ranging from 0.24 to 0.37 and an outlet vapour quality around 1.00. The global uncertainty of the local heat transfer coefficient measurement is within ±12.7%, and ±15.6%, for R290, and R1270, respectively. Nucleate boiling seems to be the governing heat transfer regime both in R290 and R1270 tests. Consolidated correlations for nucleate boiling inside BPHE show a fair agreement with all the experimental data. R290 and R1270 exhibit boiling heat transfer performance between those of R404A and those of R410A.
File in questo prodotto:
Non ci sono file associati a questo prodotto.
Pubblicazioni consigliate

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11577/3507329
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 1
  • ???jsp.display-item.citation.isi??? 1
social impact